Construction Performance Guidelines
Article Number
5.24
Condition
SKYLIGHT LEAKS
Acceptable Performance/Condition
Skylights shall be installed in accordance with the manufacturer’s specifications and shall not allow water penetration.
Warranty
Two-Year - Building Envelope Water Penetration. · Damage resulting from dampness or condensation due to failure by the homeowner to maintain adequate ventilation is not covered by the statutory warranty.
Action
Skylights not meeting the acceptable performance shall be repaired.
Remarks