Wall Is Out Of Plumb

Article Number

3.1

Condition

WALL IS OUT OF PLUMB

Acceptable Performance/Condition

Where the condition is visible from a normal viewing position, walls shall not be out of plumb more than 19 mm in 2,400 mm vertical measurement.

Warranty

One-Year - Work and Materials.

Action

Walls not meeting the acceptable condition shall be repaired.

Remarks

It is reasonable to expect minor variation from plumb. Fitment of furnishings is not considered to be the test for plumb. See Also: 3.2 WALL IS BOWED 9.3 GYPSUM WALLBOARD CORNERS ARE UNEVEN

  