Construction Performance Guidelines
Article Number
3.1
Condition
WALL IS OUT OF PLUMB
Acceptable Performance/Condition
Where the condition is visible from a normal viewing position, walls shall not be out of plumb more than 19 mm in 2,400 mm vertical measurement.
Warranty
One-Year - Work and Materials.
Action
Walls not meeting the acceptable condition shall be repaired.
Remarks
It is reasonable to expect minor variation from plumb. Fitment of furnishings is not considered to be the test for plumb. See Also: 3.2 WALL IS BOWED 9.3 GYPSUM WALLBOARD CORNERS ARE UNEVEN